F-Values for Below Grade Floors & Walls (Heated Basement)
|
|
Heat Loss by Perimeter Length (BTUH/*F/Ft.)***
|
|
Depth Below Grade in Feet
|
Wall Insulation (Floor Uninsulated)
|
|
R0
|
R4
|
R7
|
R11
|
R19
|
|
1'
|
0.84
|
0.58
|
0.54
|
0.51
|
0.48
|
|
2'
|
0.97
|
0.61
|
0.54
|
0.48
|
0.43
|
|
3'
|
1.06
|
0.65
|
0.56
|
0.48
|
0.41
|
|
4'
|
1.14
|
0.7
|
0.59
|
0.5
|
0.41
|
|
5'
|
1.22
|
0.76
|
0.64
|
0.54
|
0.43
|
|
6'
|
1.28
|
0.82
|
0.69
|
0.58
|
0.45
|
|
7'
|
1.34
|
0.87
|
0.73
|
0.61
|
0.48
|
|
|
Duct Losses per Lineal Foot
|
|
Rated
Value of Duct Insulation
|
R0
|
R2
|
R4
|
R7
|
R9
|
R11
|
R19
|
|
kWh/ft.
|
18.8
|
9.2
|
4.3
|
2.8
|
2
|
1.7
|
1.2
|
|
|
|
Exterior Wall Insulation To 2-Feet
Below Grade
|
|
|
R0
|
R4
|
R8
|
R10
|
|
F-Value
(BTUH/*F/Ft)
|
1.28
|
0.92
|
0.82
|
0.79
|
|
|
Hydronic Pipe Losses per Lineal Foot
|
|
Nominal
Value of Pipe Insulation
|
R0
|
R4
|
|
kWh/ft.
|
2.2
|
0.94
|
|
|
Concrete Slab Floor on Grade
|
|
F-Value (BTUH/*F/Ft)
|
Perimeter Slab Insulation
|
|
None
|
1"
|
2"
|
|
0.81
|
0.62
|
0.55
|
|
|
U-Values for Exterior Doors
|
|
Door Type
|
U-Value
|
|
Wood*
|
Without
Storm Door
|
0.46
|
|
With
Storm Door
|
0.31
|
|
Door
to Buffer Space
|
0.41
|
|
Door
w/Storm to Buffer
|
0.28
|
|
French Doors
|
Without
Storm Door
|
0.61
|
|
With
Storm Door
|
0.34
|
|
Metal Foam Core
|
Without
Storm Door
|
0.14
|
|
With
Storm Door
|
0.12
|
|
Door
to Buffer Space
|
0.13
|
|
|